SHOCK HAZARD. Turn off AC power before making any rear panel connections. Ensure that MagnaDC power supply connections, load wiring, and load connections are either insulated or covered so that no accidental contact with lethal output voltages can occur.
The DC output of the TS Series MagnaDC power supply connects to the DC bus by attaching two cables to the output bus bars. Magna-Power recommends DC power cables be crimped to ring terminals and securely fastened to bus bars using the included 3/8” bolts, washers, and lock washers. The bus bars contain 3/8”-16 threaded inserts. The recommended torque for the DC connection is 240 in-lbf (27.1 Nm).
Select a wire size sufficient to handle the maximum output current of the unit, no matter what the intended load current or current limit setting.
The recommended wire size for different current levels are shown in the table below.
Wire Size (USA) |
Equivalent Wire Size
(International)
|
Wires Per Output Terminal |
Maximum Current |
|---|---|---|---|
6 AWG |
10 mm2 |
1 |
85 Adc |
4 AWG |
25 mm2 |
1 |
110 Adc |
3 AWG |
25 mm2 |
1 |
130 Adc |
2 AWG |
35 mm2 |
1 |
150 Adc |
1 AWG |
50 mm2 |
1 |
170 Adc |
1/0 AWG |
50 mm2 |
1 |
200 Adc |
2/0 AWG |
70 mm2 |
1 |
235 Adc |
3/0 AWG |
95 mm2 |
1 |
275 Adc |
4/0 AWG |
120 mm2 |
1 |
315 Adc |
1/0 AWG |
50 mm2 |
2 |
400 Adc |
2/0 AWG |
70 mm2 |
2 |
470 Adc |
3/0 AWG |
95 mm2 |
2 |
550 Adc |
4/0 AWG |
120 mm2 |
2 |
630 Adc |
1/0 AWG |
50 mm2 |
4 |
800 Adc |
2/0 AWG |
70 mm2 |
4 |
940 Adc |
3/0 AWG |
95 mm2 |
4 |
1100 Adc |
4/0 AWG |
120 mm2 |
4 |
1260 Adc |
Notes:
Capacity for AWG wires derived from the National Electric Code. Maximum ambient temperature: 40°C. Maximum wire temperature: 90°C. Continuous duty with wires in free air, not bundled or in conduit.
Capacity of aluminum wire is approximately 84% of the capacity listed for copper wire.
For higher current levels, it’s recommended to use bus bars with holes for additional cable feeds or direct bus bar connection to the load.
Warning
FIRE HAZARD. Select a wire size large enough to carry the TS Series MagnaDC power supply model’s maximum rated current to prevent overheating of the wires. Make sure power cable connections are secured tightly in accordance with the torque recommendation to prevent overheating of the bus bars.
3.5.1. Grounding the DC Output
The output of the TS Series MagnaDC power supply is floating up to the DC output isolation specifications. A floating output means the output terminals are not connected electrically to ground and the produced output voltage is from the positive terminal with respect to the negative terminal. Neither output terminal needs to be connected to ground, however if desired, either the positive or negative terminal can be connected to earth ground.