SHOCK HAZARD. Depending on the application, high voltages hazardous to human safety may be present on the output terminals of the MagnaDC power supply during normal operation. Disconnect AC power from the mains and open the AC input breaker before attempting any installation procedure. Ensure that the output power cables are properly labeled as to the safety hazards and that any inadvertent contact with hazardous voltages is eliminated.

DC power is wired to the MT Series MagnaDC power supply by attaching two cables to the output bus bars at the rear of the cabinet. Magna-Power recommends DC power cables be crimped to ring terminals and securely fastened to the bus bars using the included 3/8” hardware. The recommended torque for the DC connection is 240 in-lbf (27.1 Nm).

The bus configuration depends on the model’s rated output voltage; refer to Product Diagrams for the arrangement, hole pattern, and dimensions of each variant. Mating hardware is included with each output bus.

  • Models rated below 60 Vdc: 3/8”-16 threaded inserts, quantity (4) per output bus.

  • Models rated 60 Vdc through 1000 Vdc: 0.41 in (1.04 cm) diameter holes, quantity (4) per output bus.

  • Models rated above 1000 Vdc or with the High Isolation Output Option (+ISO): 0.39 in (0.99 cm) diameter hole, quantity (1) per output bus.

Where the bus provides four connection points per output, distribute the conductors across the available points rather than stacking them all on one.

Caution

Make sure connections are tight and torqued to the recommendation above to avoid overheating of the bus bars. At the currents the MT Series delivers, a loose or partially seated connection will overheat well before any protective device responds.

Wire Size (USA)

Equivalent Wire Size
(International)

Wires Per Output Terminal

Maximum Current

6 AWG

10 mm2

1

85 Adc

4 AWG

25 mm2

1

110 Adc

3 AWG

25 mm2

1

130 Adc

2 AWG

35 mm2

1

150 Adc

1 AWG

50 mm2

1

170 Adc

1/0 AWG

50 mm2

1

200 Adc

2/0 AWG

70 mm2

1

235 Adc

3/0 AWG

95 mm2

1

275 Adc

4/0 AWG

120 mm2

1

315 Adc

1/0 AWG

50 mm2

2

400 Adc

2/0 AWG

70 mm2

2

470 Adc

3/0 AWG

95 mm2

2

550 Adc

4/0 AWG

120 mm2

2

630 Adc

1/0 AWG

50 mm2

4

800 Adc

2/0 AWG

70 mm2

4

940 Adc

3/0 AWG

95 mm2

4

1100 Adc

4/0 AWG

120 mm2

4

1260 Adc

Notes:

  1. Ampacities are derived from the National Electrical Code.

  2. Values assume a 40 °C ambient and 90 °C rated wire.

  3. Aluminum conductors carry approximately 84% of the ampacity of an equivalently sized copper conductor.

  4. For output currents beyond the range of a single conductor, use multiple conductors in parallel or bus bars sized for the application.

Warning

FIRE HAZARD. Select a wire size large enough to carry the MT Series MagnaDC power supply model’s maximum rated current to prevent overheating of the wires. Make sure power cable connections are secured tightly in accordance with the torque recommendation to prevent overheating of the bus bars.

After the output connections are made and verified, install the protective covers over the output bus as described in Protective Covers.

3.4.1. Grounding the DC Output

The DC output of the MT Series MagnaDC power supply is floating with respect to earth ground, and either output terminal may be earthed to establish a ground reference for the application. The maximum permissible potential from either output terminal to ground depends on the model and on whether the High Isolation Output option is fitted; refer to the DC Output Isolation entries under Output Specifications.

Warning

Do not exceed the published output isolation rating. Grounding one output terminal of a series-connected string can place the far end of the string well above the isolation rating of an individual unit. See Parallel and Series before series-connecting units.