2.5. Specifications

2.5.1. AC Input Specifications

3Φ AC Input Voltage
3Φ, 3-wire + ground
Available on all models
380/400 Vac (operating range 342 to 440 Vac)
415 Vac (operating range 373 to 456 Vac)
440 Vac (operating range 396 to 484 Vac)
480 Vac (operating range 432 to 528 Vac)

AC Input Current

Refer to AC Input Current

AC Input Frequency

50-60 Hz

Power Factor

>0.92 at max power; 150 kW models
>0.96 at max power; 250 kW models

AC Input Isolation

±2500 Vdc, maximum input voltage to ground

2.5.2. Output Specifications

Voltage Ripple

Refer to chart of available models.

Line Regulation

Voltage mode: ± 0.004% of full scale
Current mode: ± 0.02% of full scale

Load Regulation

Voltage mode: ± 0.01% of full scale
Current mode: ± 0.04% of full scale

Load Transient Response

2 ms to recover within ±1% of regulated output with a 50% to 100% or 100% to 50% step load change

Stability

± 0.10% for 8 hrs. after 30 min. warm-up

Efficiency

90% to 92%; refer to chart of available models

DC Output Isolation
Models Rated ≤1000 Vdc

±1000 Vdc, max output voltage to ground

DC Output Isolation
Models Rated >1000 Vdc or
Models with +ISO Option

±6000 Vdc, max output voltage to ground

2.5.3. Programming Specifications

Programming Accuracy

Voltage: ±0.075% of max voltage rating
Current: ±0.075% of max current rating

Measurement Accuracy

Voltage: ±0.2% of max voltage rating
Current: ±0.2% of max current rating
Maximum Slew Rate
Standard Models
<170 ms, output voltage change from 0 to 63%
<200 ms, output current change from 0 to 63%
Maximum Slew Rate
Models with High Slew Rate Option (+HS)
<5 ms, output voltage change from 0 to 63%
<10 ms, output current change from 0 to 63%
Bandwidth
Standard Models
3 Hz, remote analog voltage
2 Hz, remote analog current
Bandwidth
Models with High Slew Rate Option (+HS)
60 Hz, remote analog voltage
45 Hz, remote analog current

Trip Settings Range

Over Voltage: 10% to 110% max voltage rating
Over Current: 10% to 110% max current rating

Computer Command Protocol

Standard Commands for Programmable Instruments (SCPI)

Remote Sense Limits
Wired; Available on Models Rated ≤1000 Vdc
without the +ISO Option

3% maximum voltage drop from output to load

2.5.4. Connectivity Specifications

Communication Interfaces (Standard)

RS232: DB-9, Female
External User I/O: DB-37, Female

Communication Interfaces (Optional)

LXI TCP/IP Ethernet: RJ-45
GPIB: IEEE-488

2.5.5. External User I/O Specifications

Digital Inputs

5 V, 10 kΩ impedance

Digital Monitoring Signals

5 V, 5 mA capacity

Digital Reference Signal

5 V output, 25 mA capacity

Analog Programming Input

0-10 V

Analog Programming Impedance

10 kΩ

Analog Monitoring Signals

0-10 V, 5 mA capacity

Analog Monitoring Impedance

100 Ω

Analog Monitoring Accuracy

0.2% of max rating

Analog Reference Signal

10 V, 5 mA capacity, 1 Ω impedance

For more details about the External User I/O, see: Operation: External User I/O.

2.5.6. Physical Specifications

Power Level

Cabinet

Size

Weight

150 kW

Floor-standing double-bay 19” cabinet
Qty (6) locking casters, standard
67” H x 48” W x 31.5” D
(170.2 x 121.9 x 80.0 cm)

2100 lbs (952.5 kg)

250 kW

Floor-standing triple-bay 19” cabinet
Qty (8) locking casters, standard
67” H x 72” W x 31.5” D
(170.2 x 182.9 x 80.0 cm)

3300 lbs (1496.9 kg)

2.5.7. Environmental Specifications

Ambient Operating Temperature

0°C to 50°C

Storage Temperature

-40°C to +85°C

Humidity

Relative humidity up to 95% non-condensing

Air Cooling

Front and rear air inlet, top exhaust

Temperature Coefficient

0.04%/°C of maximum output voltage
0.06%/°C of maximum output current

2.5.8. Regulatory Compliance

EMC

Complies with 2014/30/EU (EMC Directive)
CISPR 22 / EN 55022 Class A

Safety

Complies with EN61010-1
Complies with 2014/35/EU (Low Voltage Directive)

CE Mark

Yes

RoHS Compliant

Yes