3.6. Remote Sense Connection
Remote sensing can improve regulation at a remote reference point. For example, appreciable voltage drop can occur in the wire between the power supply and load as the current increases. By default, the MagnaDC power supply operates in local sense, with feedback taken at its output terminals. In remote sense, the MagnaDC power supply makes up for lead voltage drop through high-impedance sense wires connected at the load. When the remote sense setting is enabled, the feedback measurements are taken from the remote sense leads.
The remote sense setting is accessible from either the front panel configuration or by computer command. Remote sense is a differential signal, so make both sense connections at the point of load: the MagnaDC power supply’s positive remote sense lead to the positive load terminal, and its negative remote sense lead to the negative load terminal.
Caution
Always ensure that the positive remote sense lead corresponds to the positive DC bus and, likewise, the negative remote sense lead corresponds to the negative DC bus. Connecting sense wires with an incorrect polarity can result in equipment damage.
The remote sense terminals use #6-32 hardware. A screw, flat washer, and split lock washer are provided for each terminal. Crimp an insulated #6 ring terminal onto each sense lead and fasten it to its terminal with the provided hardware. At the far end of each lead, use a ring terminal sized for the stud or screw it fastens to. Use wire with insulation rated for at least the highest voltage the sense leads reach with respect to ground. Twist the positive and negative sense leads together and route them away from the DC power cables.
Warning
Shock Hazard The remote sense leads carry the full DC bus voltage. Insulate or cover the sense connections at both ends so that no accidental contact with live parts can occur.
Remote sense compensates for up to 4% of the MagnaDC power supply’s rated voltage, measured as the total drop across both leads. In remote sense mode, the MagnaDC power supply compares the remote sense voltage to the local sense voltage. If the difference exceeds the 4% compensation limit, the MagnaDC power supply may stop with a Remote Sense Loss soft fault. This check protects against an open or miswired sense lead. Without it, the voltage error would stay positive, and the MagnaDC power supply would raise its output past its voltage rating.