4. Paralleling
The SLx Series MagnaDC power supply supports two architectures for operating multiple units with their outputs connected in parallel, delivering current beyond the rating of a single unit. In MagnaLINK Master-Slave operation, units are synchronized over MagnaLINK™ and behave as a single higher-power product: the master provides a single point of control, aggregates measurements across the system, and shares the load equally among the units. In Direct Parallel operation, units operate independently on a common output bus with no inter-unit communication, trading single-point control and aggregated measurement for redundancy and scalability: because no unit depends on another, the loss of a single unit does not take the system offline, and the architecture scales past the Master-Slave unit-count ceiling.
Attribute |
Master-Slave |
Direct Parallel |
|---|---|---|
Inter-unit communication |
MagnaLINK™ |
None |
Control |
Single point (via master) |
Each unit controlled independently |
Measurement aggregation |
Yes |
No |
Load sharing |
Equal across units |
Unequal (see Direct Parallel) |
Redundancy |
None — one failure takes the whole system offline |
Automatic — regulation transfers to another unit; others keep supplying the load |
Maximum units |
12 |
No limit encountered to date |
Setup |
Plug-and-play auto-configuration |
Stagger voltage set-points per unit |
Note
Do not mix Master-Slave and Direct Parallel units in the same system; operate every unit in the system in the same mode. Magna-Power Electronics validates each specific parallel configuration in its test department prior to shipment.