3.4. AC Input Connection

Warning

Disconnect AC power from the mains and measure the AC input terminals to ground to ensure 0 Vac is present before attempting any installation procedure.

AC power is wired to the ML Series MagnaDC power supply by attaching three cables plus ground. A safety ground wire must be connected to the stud labeled with a ground symbol. The ML Series is insensitive to phase orientation, so the three phase conductors may be connected to the input bus bars in any order.

The user AC connection is made at the harmonic neutralizer, which is where the system circuit breaker is located. On 500 kW models the neutralizer is part of the connected three-cabinet assembly; on 1000 kW models it is the second cabinet, interconnected as described in Harmonic Neutralizer Interconnection.

The AC input connection points are three copper bus bars located behind a cover/access panel at the rear of the cabinet, dimensioned in Fig. 2.5. Conductors should be terminated with a 3/8” ring terminal to mate with the provided hardware. The recommended torque for the AC input connection is 240 in-lbf (27.1 Nm). Each bus bar accepts connections on both faces, so conductors may be landed from either side.

Magna-Power recommends cables per the recommendations of the National Electrical Code or Suggested Ampacities of 4-Conductor Type S or SO Cable, crimped to ring terminals and securely fastened to the bus bars.

Note

The cable recommendations provided are for reference purposes only. Always consult local electrical code requirements to ensure compliance.

Given the input currents involved, verify that every connection is tight before energizing the supply. A loose connection at these current levels will overheat the bus and the cable termination well before any protective device responds.

This programmable DC power supply is designed to be permanently connected to the power source, requiring a readily accessible disconnect device incorporated into the fixed wiring. The integrated AC input breaker described in Circuit Breaker is not a substitute for that disconnect device.

Table 3.2 Suggested Ampacities of Various Conductors as Recommended by the National Electrical Code

Wire Size

60 °C Types

75 °C Types

85 °C Types

90 °C Types

RUW, T, TW

FEPW, RH, RH, RUH, THW, THWN, XHHW, ZW

V, MI

TA, TBS, SA, AVB, SIS, FEP, FEPB, RHH, THHN, XHHW

14 AWG

25 Aac

30 Aac

30 Aac

35 Aac

12 AWG

30 Aac

35 Aac

40 Aac

40 Aac

10 AWG

40 Aac

50 Aac

55 Aac

55 Aac

8 AWG

60 Aac

70 Aac

75 Aac

80 Aac

6 AWG

80 Aac

95 Aac

100 Aac

105 Aac

4 AWG

105 Aac

125 Aac

135 Aac

140 Aac

3 AWG

120 Aac

145 Aac

160 Aac

165 Aac

2 AWG

140 Aac

170 Aac

185 Aac

190 Aac

1 AWG

165 Aac

195 Aac

215 Aac

220 Aac

10 AWG

195 Aac

230 Aac

250 Aac

260 Aac

20 AWG

225 Aac

265 Aac

290 Aac

300 Aac

30 AWG

260 Aac

310 Aac

335 Aac

350 Aac

40 AWG

300 Aac

360 Aac

390 Aac

405 Aac

250 MCM

340 Aac

405 Aac

440 Aac

455 Aac

300 MCM

375 Aac

445 Aac

485 Aac

505 Aac

350 MCM

420 Aac

505 Aac

550 Aac

570 Aac

Table 3.3 Suggested Ampacities of 4-Conductor Type S or SO Cable

Wire Size

Maximum Current

18 AWG

7 Aac

16 AWG

10 Aac

14 AWG

15 Aac

12 AWG

20 Aac

10 AWG

25 Aac

8 AWG

35 Aac

6 AWG

45 Aac

4 AWG

60 Aac

2 AWG

80 Aac

3.4.1. AC Input Current

The following table provides the maximum input current rating per phase for the available AC input voltages and power levels of the ML Series. All AC input currents factor in efficiency and power factor. With the product’s AC soft-start circuitry, there is no additional in-rush current; the numbers in the following table provide the peak AC current draw at full load. These same AC input current ratings are also specified on the product’s serial label. These ratings, in combination with the conductor ampacity tables above, guide AC input conductor selection.

Table 3.4 AC input current ratings for ML Series MagnaDC power supply

Power Level

AC Input Voltage

AC Input Current

500 kW

440 Vac, 3Φ

760 Aac

500 kW

480 Vac, 3Φ

697 Aac

1000 kW

440 Vac, 3Φ

1519 Aac

1000 kW

480 Vac, 3Φ

1362 Aac

Note

For master-slave systems, each cabinet draws the current listed above and must be provided with its own branch circuit sized accordingly.

3.4.2. Circuit Breaker

The ML Series MagnaDC power supply is equipped with an integrated three-phase AC breaker rated for the full power of the supply, housed in the harmonic neutralizer section and accessible from the rear of the cabinet. This is a difference from the smaller MagnaDC products, which protect the power stage with input power and control fuses instead: the ML Series has no input fuses to inspect or replace.

The breaker serves two purposes. It provides overcurrent protection for the power processing circuitry, and it isolates the unit from the mains for service. The breaker must be in the on position for the supply to operate.

If the breaker trips, or if the breaker has not been engaged after turning on control power at the front panel control power switch, the fuse (FSE) alarm will indicate. Investigate the cause before re-engaging the breaker: a tripped breaker usually indicates a power stage failure, often requiring factory attention, though it can also be caused by power surges from lightning storms or other AC transient events. After engaging the breaker to the on position, clear the FSE alarm as described in Fuse (FSE).

Warning

Lethal voltages may be present inside the power supply even when the AC input breaker is open and the AC input voltage is disconnected. Only properly trained and qualified personnel should remove covers and access the inside of the power supply.