2.5. Specifications

2.5.1. AC Input Specifications

Input Voltages Available
AC Input voltage specified at time of order and cannot be modified
440 Vac, 3-phase
480 Vac, 3-phase
Input Voltage Tolerance
± 10%
Input Voltage Frequency
50-60 Hz
Power Factor
Measured at max power
> 0.96
Input Isolation
Measured line-to-ground
± 2000 Vdc
AC Circuit Protection
UL/CSA listed circuit breaker

2.5.2. Output Specifications

Voltage Ripple
Model specific. Refer to models table.
Line Regulation
Voltage control: ± 0.04% of rated voltage
Current control: ± 0.03% of rated current
Load Regulation
Voltage control: ± 0.02% of rated voltage
Current control: ± 0.06% of rated current
Stability
FWHM, measured at 25°C over 8 hrs after 30 min warm-up
± 0.10%
Temperature Coefficient
Voltage control: 0.04%/°C of rated voltage
Current control: 0.06%/°C of rated current
Efficiency
Up to 96%. Model specific. Refer to Models table.
Slew Rate
Standard models
< 170 ms, output voltage change from 0 to 63%
< 200 ms, output current change from 0 to 63%
Slew Rate
Models with High Slew Rate (+HS) Option
< 5 ms, output voltage change from 0 to 63%
< 10 ms, output current change from 0 to 63%
Output Isolation
Measured output-to-ground
Models rated ≤ 1000 Vdc
± 1500 Vdc
Output Isolation
Measured output-to-ground
Models rated > 1000 Vdc or models with
High Isolation Output (+ISO) option
± 6000 Vdc

2.5.3. Programming Specifications

Resolution, Digital Programming
Front panel or communication interfaces
12-bit, 0.025% of rated voltage, current or power
Accuracy, Programming
Output value to set point value
Voltage: ± 0.075% of rated voltage
Current: ± 0.075% of rated current
Accuracy, Measurement
Output value to returned value
Voltage: ± 0.20% of rated voltage
Current: ± 0.20% of rated current
Trip Settings Range
Over Voltage: 10% to 110% of rated voltage
Over Current: 10% to 110% of rated current
Computer Command Protocol
Standard Commands for Programmable Instruments (SCPI) (ASCII-based commands)
Remote Sense Limits
Wired; Available on models rated ≤ 1000 Vdc
3% maximum voltage drop from output to load
Analog I/O
4 analog programming inputs
2 analog measurement outputs
Reference signal provided
Analog programming inputs: 0-10 V
Analog programming impedance: 10 kΩ
Analog measurement outputs: 0-10V, 5 mA capacity
Analog measurement impedance: 100 Ω
Analog reference signal: 10 V, 5 mA capacity, 1 Ω
Digital I/O
5 digital control inputs
15 digital monitoring outputs
Reference signal provided
Digital control inputs: 5 V
Digital control inputs impedance: 10 kΩ
Digital monitoring outputs: 5 V, 5 mA capacity
Digital reference signal: 5 V, 25 mA capacity

2.5.4. Connectivity Specifications

Front Panel Programming
Two machined aluminum 10-turn knobs and keypad
Communication Interfaces
Standard
RS232: D-sub DB-9, Female
External User I/O Port
Standard
37-pin D-sub DB-37, female
Referenced to ground; isolated from the DC output
See External User I/O for the pin layout
Communication Interfaces
Optional
LXI TCP/IP Ethernet (+LXI): RJ-45

2.5.5. External User I/O Specifications

Digital Inputs

5 V, 10 kΩ impedance

Digital Monitoring Signals

5 V, 5 mA capacity

Digital Reference Signal

5 V output, 25 mA capacity

Analog Programming Input

0-10 V

Analog Programming Impedance

10 kΩ

Analog Monitoring Signals

0-10 V, 5 mA capacity

Analog Monitoring Impedance

100 Ω

Analog Monitoring Accuracy

0.2% of max rating

Analog Reference Signal

10 V, 5 mA capacity, 1 Ω impedance

For more details about the External User I/O, see: Operation: External User I/O.

2.5.6. Physical Specifications

Size & Weight
500 kW models
Ships as a single, connected three-cabinet assembly:

500 kW Power Supply and Harmonic Neutralizer
76.4” H x 72” W x 31.5” D (194.1 x 182.9 x 80.0 cm)
6800 lbs (3084 kg)
7300 lbs (3311 kg) crated
Size & Weight
1000 kW models
Ships as two components:

1000 kW Power Supply
76.4” H x 72” W x 31.5” D (194.1 x 182.9 x 80.0 cm)
5500 lbs (2495 kg) crated

1000 kW Harmonic Neutralizer
76.4” H x 48” W x 31.5” D (194.1 x 121.9 x 80.0 cm)
5000 lbs (2268 kg) crated
Shipping Envelope
1000 kW models
Power Supply skid: 84” L x 72” W x 84” H (213.4 x 182.9 x 213.4 cm)
Harmonic Neutralizer skid: 60” L x 72” W x 84” H (152.4 x 182.9 x 213.4 cm)

2.5.7. Environmental Specifications

Ambient Operating Temperature
0°C to 50°C
Storage Temperature
-40°C to +85°C
Humidity
Relative humidity up to 95% non-condensing
Air Flow
To ensure even heat distribution for the water cooling system
Bottom air inlet, top exhaust
Coolant Supply
Requirement for user-supplied coolant
Maximum inlet temperature: 25°C
Maximum inlet pressure: 80 psi
Inlet and outlet fittings provided: 1” Female NPT
Materials in coolant path: Copper pipe, PEX tubing, brass solenoid & fittings
Coolant Connections
One inlet and one outlet, on the power supply
1000 kW models: the harmonic neutralizer is fed from the power supply through an internal quick disconnect
Minimum Coolant Flow Rate
500 kW models
9 GPM
Minimum Coolant Flow Rate
1000 kW models
15 GPM
Heat Rejection
Distribution of total losses
Approximately 80% to the coolant, 20% to ambient air

2.5.8. Regulatory Compliance

EMC
Complies with 2014/30/EU (EMC Directive)
CISPR 22 / EN 55022 Class A
Safety
Complies with EN61010-1 and 2014/35/EU (Low Voltage Directive)
CE Mark
Yes
UKCA Mark
Yes
RoHS Compliant
Yes
REACH Compliant
Yes