3.4. Specifications¶
The following specifications are subject to change without notice. Unless otherwise noted, all specifications measured at the product’s maximum ratings.
3.4.1. AC Input Specifications¶
1Φ AC Input Voltage
1Φ, 2-wire + ground
|
85 to 265 Vac |
AC Input Connector |
IEC 60320 C13 receptacle |
AC Input Frequency |
50-60 Hz |
AC Input Isolation |
±1500 Vac, maximum input voltage to ground |
3.4.2. DC Input/Output Specifications¶
DC Input
Configuration A1, B1 Only
|
Qty (2) 0.25” x 0.75” tin plated copper bus bar
3/8”-16 threaded insert on each bus bar
250 Adc maximum
|
DC Input
Configuration A1, B1 Only
|
Qty (2) 0.25” x 0.75” tin plated copper bus bar
3/8”-16 threaded insert on each bus bar
|
3.4.3. Performance Specifications¶
Stability, FWHM
Voltage Control
|
< 10 ppm; long-term drift (8 hr) |
Stability, FWHM
Current Control
|
< 10 ppm; long-term drift (8 hr) |
Temperature Coefficient
Voltage Control
|
< 0.05 ppm/°C |
Temperature Coefficient
Current Control
|
< 0.5 ppm/°C |
Programming Resolution |
18-bit |
Measurement Resolution |
24-bit |
Accuracy
Programmaing and Measurement
|
± 0.04% |
Rise/Fall Time, Maximum |
Voltage Mode: 6 s, 10% to 90% max voltage
Current Mode: 6 s, 10% to 90% max current
Power Mode: 6 s, 10% to 90% max power
|
Power Loss
Configuration A1 Only
|
Current output x 1.5 volts |
Warm-up Time |
45 min |
3.4.4. External User I/O Specifications¶
For more details about the External User I/O, see: Operation: External User I/O.
3.4.5. Connectivity Specifications¶
Communication Interfaces (Standard) |
USB Host (Front): Type B
USB Host (Rear): Type B
RS485 (Rear): RJ-45
DBx Interface I/O: 15-pin D-Sub, female
External Interface I/O: 25-pin D-Sub, female
|
Communication Interfaces (Optional) |
LXI TCP/IP Ethernet: RJ-45
EtherNet/IP: Dual RJ-45
|
3.4.6. Physical Specifications¶
Racking Standard |
EIA-310 |
Rear Support Rails |
Included |
Size and Weight
Configuration A1, B1
|
1U
1.75” H x 19” W x 24” D
(4.4 x 48.3 x 61.0 cm)
35 lbs (15.88 kg)
|
Size and Weight
Configuration C1
|
1U (See Above) + External Transducer
External transducer size and weight will vary depending on current rating
|
3.4.7. Environmental Specifications¶
Ambient Operating Temperature |
0°C to 50°C |
Storage Temperature |
-25°C to +85°C |
Humidity |
Relative humidity up to 95% non-condensing |
Air Flow |
Side air inlet, rear exhaust |
3.4.8. Regulatory Compliance¶
EMC |
Complies with 2014/30/EU (EMC Directive)
CISPR 22 / EN 55022 Class A
|
Safety |
Complies with EN61010-1
Complies with 2014/35/EU (Low Voltage Directive)
|
CE Mark |
Yes |
RoHS Compliant |
Yes |